Most of what a field node runs sits between the sensor and the actuator: turning counts into units, discarding a bad sample, deciding whether to switch something on. pamoja-kit is that layer. The helpers are named for the goal rather than the technique, with the algorithm one level down: a Smoother is an exponential moving average, a Thermostat is a bang-bang controller with hysteresis, a Depletion is a projected countdown. They are synchronous and allocation-free, so the same code runs on a gateway and on a microcontroller.

The rest of the set has the same shape. Pid and Ramp drive a continuous output, Debounce cleans up a noisy contact, Window and Trend summarise recent readings, Surge and Anomaly catch a reading that is moving or sitting where it should not be, Geofence says where a tracked thing is, and the kinematics cover a wheeled chassis and a jointed arm.

What the example does#

It reads a tank level off a 4-20 mA current loop. A two-point calibration converts the loop current into a percentage, a median window discards a momentary dropout, and a hysteresis controller decides whether the refill pump runs.

The calibration is built from the two ends of the loop, 4 mA empty and 20 mA full, rather than from a slope and an offset worked out by hand, so a reader sees the currents the loop is specified by. The first level the pump sees is not typed in either; it is the filtered, calibrated reading carried down from the stage above. The three that follow are typed in, to walk the controller below the deadband, back inside it, and out the top.

It proves:

  • 12 mA reads 50% and 4 mA reads 0%, because the span starts at 4 mA and not at zero; a map scaled from zero would put mid-scale at 60% and still be self-consistent.
  • 0 mA reads -25%, off the bottom of the scale, which is what separates a broken loop from an empty tank.
  • One dropout among five samples leaves the filtered level at 50%, where a mean over the same window would be dragged down by it.
  • At the setpoint the pump stays off, and it starts only once the level falls below the deadband.
  • Once running it keeps running at a level back inside the deadband, and stops only above the top of it.

The windowed helpers keep the most recent readings and nothing older. In Rust the window length is a const generic chosen at the call site; the bindings fix it at 32 readings. Five readings fit in either window, so the same samples give the same median in all four languages.

Rust#

From examples/tests/guides/kit.rs:

Rust
use pamoja_kit::{Calibration, Median, Thermostat};

// A 4-20 mA process loop carries the level as a current: 4 mA is empty and 20 mA is
// full, so the span is 16 mA and mid-scale is 12 mA, not 10.
let level = Calibration::two_point(4.0, 0.0, 20.0, 100.0);
let (mid, empty) = (level.apply(12.0), level.apply(4.0));
println!("12 mA is {mid}% full, 4 mA is {empty}%");

// The live zero is what makes a broken loop detectable: 0 mA is off the bottom of the
// scale rather than an empty tank.
let broken = level.apply(0.0);
println!("a dead loop reads {broken}%, which is not a level at all");

// A median window drops that sample outright, where an average would blend a quarter
// of the range into every reading after it.
let mut filtered = Median::<5>::new();
let mut percent = 0.0;
for milliamps in [12.0, 12.0, 0.0, 12.0, 12.0] {
    percent = level.apply(filtered.update(milliamps));
}
println!("through the dropout, the level held at {percent}%");

// A refill pump runs when the level falls below the deadband, which is the direction
// `heating` names; nothing about it is specific to temperature. The deadband stops a
// level sitting on the threshold from chattering the contactor.
let mut pump = Thermostat::heating(50.0, 10.0);
for reading in [percent, 38.0, 45.0, 62.0] {
    let running = if pump.update(reading) { "on" } else { "off" };
    println!("at {reading}% the pump is {running}");
}

TypeScript#

From bindings/node/guides/kit.ts:

TypeScript
import { Calibration, Median, Thermostat } from '@pamoja/kit'

// A 4-20 mA process loop carries the level as a current: 4 mA is empty and 20 mA is full,
// so the span is 16 mA and mid-scale is 12 mA, not 10.
const level = Calibration.twoPoint(4, 0, 20, 100)
console.log(`12 mA is ${level.apply(12)}% full, 4 mA is ${level.apply(4)}%`)

// The live zero is what makes a broken loop detectable: 0 mA is off the bottom of the
// scale rather than an empty tank.
const broken = level.apply(0)
console.log(`a dead loop reads ${broken}%, which is not a level at all`)

// A median window drops that sample outright, where an average would blend a quarter of
// the range into every reading after it.
const filtered = new Median()
let percent = 0
for (const milliamps of [12, 12, 0, 12, 12]) {
  percent = level.apply(filtered.update(milliamps))
}
console.log(`through the dropout, the level held at ${percent}%`)

// A refill pump runs when the level falls below the deadband, which is the direction
// heating names; nothing about it is specific to temperature. The deadband stops a level
// sitting on the threshold from chattering the contactor.
const pump = Thermostat.heating(50, 10)
for (const reading of [percent, 38, 45, 62]) {
  console.log(`at ${reading}% the pump is ${pump.update(reading) ? 'on' : 'off'}`)
}

Python#

From bindings/python/guides/kit.py:

Python
from pamoja.kit import Calibration, Median, Thermostat

# A 4-20 mA process loop carries the level as a current: 4 mA is empty and 20 mA is full,
# so the span is 16 mA and mid-scale is 12 mA, not 10.
level = Calibration.two_point(4.0, 0.0, 20.0, 100.0)
print(f"12 mA is {level.apply(12.0)}% full, 4 mA is {level.apply(4.0)}%")

# The live zero is what makes a broken loop detectable: 0 mA is off the bottom of the
# scale rather than an empty tank.
broken = level.apply(0.0)
print(f"a dead loop reads {broken}%, which is not a level at all")

# A median window drops that sample outright, where an average would blend a quarter of
# the range into every reading after it.
filtered = Median()
percent = 0.0
for milliamps in (12.0, 12.0, 0.0, 12.0, 12.0):
    percent = level.apply(filtered.update(milliamps))
print(f"through the dropout, the level held at {percent}%")

# A refill pump runs when the level falls below the deadband, which is the direction
# heating names; nothing about it is specific to temperature. The deadband stops a level
# sitting on the threshold from chattering the contactor.
pump = Thermostat.heating(50.0, 10.0)
for reading in (percent, 38.0, 45.0, 62.0):
    running = "on" if pump.update(reading) else "off"
    print(f"at {reading}% the pump is {running}")

C##

From bindings/dotnet/samples/Pamoja.Guides/KitGuide.cs:

C#
// A 4-20 mA process loop carries the level as a current: 4 mA is empty and 20 mA
// is full, so the span is 16 mA and mid-scale is 12 mA, not 10.
Calibration level = Calibration.TwoPoint(4.0f, 0.0f, 20.0f, 100.0f);
Console.WriteLine($"12 mA is {level.Apply(12.0f)}% full, 4 mA is {level.Apply(4.0f)}%");

// The live zero is what makes a broken loop detectable: 0 mA is off the bottom of
// the scale rather than an empty tank.
float broken = level.Apply(0.0f);
Console.WriteLine($"a dead loop reads {broken}%, which is not a level at all");

// A median window drops that sample outright, where an average would blend a
// quarter of the range into every reading after it.
using var filtered = new Median();
float percent = 0.0f;
foreach (float milliamps in new[] { 12.0f, 12.0f, 0.0f, 12.0f, 12.0f })
{
    percent = level.Apply(filtered.Update(milliamps));
}

Console.WriteLine($"through the dropout, the level held at {percent}%");

// A refill pump runs when the level falls below the deadband, which is the
// direction heating names; nothing about it is specific to temperature. The
// deadband stops a level sitting on the threshold from chattering the contactor.
using var pump = Thermostat.Heating(50.0f, 10.0f);
foreach (float reading in new[] { percent, 38.0f, 45.0f, 62.0f })
{
    Console.WriteLine($"at {reading}% the pump is {(pump.Update(reading) ? "on" : "off")}");
}

Reference#